Swinger Shutdown - Only Used On Model Le4010/Le4010E; Swinger Shutdown For Zone Inputs (Software Version 5.12+) - Only Used On Model Le4010/Le4010E; Hardware Default; Communicator Reset / Update - Johnson Controls 3G4010 V4.0 Manuel D'installation

Table des Matières
Les langues disponibles

Les langues disponibles

Operating principles

Swinger shutdown - only used on model LE4010/LE4010E

To prevent "runaway" signals to the central station, the 3G4010/LE4010/LE4010E is equipped with Swinger
Shutdown which limits certain trouble events to a maximum of four reports every 24 hours. The condition restores
and the counter resets at midnight. A zone input must be physically restored when swinger shutdown is cleared
before the alarm restore reporting code is transmitted to the central station. Otherwise, the zone input is remains
in an 'off normal' state. Swinger Shutdown applies to the following trouble conditions:
System Tamper/Restore
Low Battery Trouble/Restore
TLM Trouble/Restore
Input Power Trouble/Restore
FTC Restore
Swinger shutdown for zone inputs (Software Version 5.12+) - only used on model LE4010/
LE4010E
Depending on the reporting codes programmed by Connect 24, swinger shutdown may not be applied. Reporting
codes associated with Fire, Fire Supervisory or Panic/Holdup will not have swinger shutdown applied to the Zone 1
to Zone 4 inputs when programmed.

Hardware default

A hardware default updates the unit with the latest configuration from C24 Communications if:
The device is programmed incorrectly.
The unit was installed at a different location and then relocated to a new site.
The SIM card is swapped.
To perform the hardware default, follow these steps:
1. Power down the unit (remove primary DC power and remove the backup battery) and remove all connections
to Zone1, Zone 2, PGM1 and PGM..
2. Connect a wire between Z2 (terminal 14) and PGM2 (terminal 8)or Z1 (terminal 13) and PGM1 (terminal 7).
3. Power up the radio by connecting the battery (if present) first and then primary DC power.
4. Wait for 20 seconds and then completely power down the unit.
5. Disconnect the wire between the Zone and PGM terminals.
Note: Failure to perform hardware default will result in the unit transmitting with the previously programmed
configuration.

Communicator reset / update

The device firmware can be updated over Cellular or PC-Link:
Table 6: Firmware update begins
Red
ON
When the firmware update begins, all LEDs are ON.
Table 7: Firmware update process
Red
FLASH ON
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual
Blue
ON
Blue
OFF
© 2025 Johnson Controls. All Rights Reserved.
Yellow / Green (High)
ON
Yellow / Green (High)
OFF
Yellow / Green (Low)
ON
Yellow / Green (Low)
OFF
18

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Le4010 v5.1Le4010e v5.1Dsc 3g4010cfDsc le4010cfDsc le4010ecf

Table des Matières