Installing the 3G4010 / LE4010 / LE4010E

All circuits are classified for UL installations as Power Limited/Class II Power Limited except for the battery leads
which are not power limited. Do not route any wiring over circuit boards. Maintain at least 1" (25.4mm) separation.
A minimum 1/4" (6.4mm) of separation must be maintained at all points between Power Limited wiring and all
other non-Power Limited wiring. Route wires as indicated above.
For ULC Commercial Fire Monitoring Installations, connections between the fire alarm control panel inputs /
outputs (telephone interface Tip/Ring or output relay contacts) and 3G4010/LE4010/LE4010E inputs/outputs (T1/
R1, Z1-Z4, PGM1-4) shall be run in metallic conduit within 18m(ULC) and in the same room.
Installing the 3G4010 / LE4010 / LE4010E
The 3G4010/LE4010/LE4010E requires enrollment with C24 Communications to operate. For more information,
please visit www.connect24.com, contact C24 Communications customer service at 1-888-251-7458 (US) /
1-888-955-5583 (Canada) or contact the central station to inquire if they are a C24 Communications Master Reseller.
Note: Enrollment with C24 Communications should be performed before turning on the 3G4010/LE4010/
LE4010E unit. Before inserting or removing the SIM card, please ensure the unit is turned off.

Step 1 - Initialize the 3G4010/LE4010/LE4010E with C24 Communications

To complete enrollment, a C24 profile, installer ID/PIN (or web credentials) and the 20-digit SIM number are
required.
Initialize the 3G4010/LE4010/LE4010E with C24 Communications by:
web - www.connect24.com
mobile - m.connect24.com
Note: The SIM activation process with the cellular carrier typically takes between five and ten minutes to
complete.

Step 2 - Determine the best signal location

1. Detach the front cover by removing the four screws
2. Apply power (DC and/or battery). The 3G4010/LE4010/LE4010E is now in Placement Test mode.
Step 2a – SIM Card Is Activated
When the SIM card is activated, the red LED is on solid, the blue LED is off, and the signal strength LEDs display the
average signal strength. In this state, the 3G4010/LE4010/LE4010E is registered to the cellular network.
Red
ON
If the signal strength is too low (bottom signal LED off or flashing), the 3G4010/LE4010/LE4010E moves to Step
3, scans for carriers with sufficient signal strength, and attaches to the carrier. If the 3G4010/LE4010/LE4010E is
connected to a carrier with sufficient signal strength (minimum of bottom signal strength LED on solid), it moves to
Step 4.

Step 2b - SIM card is not activated

The red LED flashes, the blue LED is off and the signal strength LEDs display the average signal strength.
Red
FLASHING
3G4010 V4.0 / LE4010 V5.1 / LE4010E V5.1 Installation manual
Blue
OFF
Blue
OFF
© 2025 Johnson Controls. All Rights Reserved.
Yellow / Green (High)
-
Yellow / Green (High)
-
Yellow / Green (Low)
-
Yellow / Green (Low)
-