WARNING: SHOCK HAZARD. May result in
Serious Injury or Death. Disconnect power
before servicing or installing the unit.
Note: This section is for installation of LU-PH3-A.
For installation of LU-PH3-B, refer to the
previous section.
1. Remove the top cover of the power interface to access
the mounting holes and terminal blocks.
2. Mount the power interface as indicated in
options 1, 2, or 3 to the right.
Note: Consider the following when choosing a
mounting location:
a. A minimum of 3 in (76 mm) is required between any
two power interfaces.
b. Mount the power interface in a position where it
can be easily located and accessed if service or
troubleshooting is necessary.
c. Any other mounting configurations will require
additional mechanical support. Improper installation
may result in hazards to personnel or property.
Note: For 277 V~ applications, a suitable barrier may
be required between the non-Class 2 and Class 2 wiring,
per local and national electrical wiring codes. For your
convenience, the power interface includes an
optional barrier.
3. Open the necessary knockouts to pass wires into the
wiring compartment.
®
Lutron Tape Light Solution
Power Interface Installation - LU-PH3-A
Option 1
Option 2
Option 3