When installed in restricted spaces (e�g� pipes, tank corners, structures) or in
agitators and other moving objects:
► To avoid malfunction and damage on sensor
and plant, adhere to a distance of the sensor
tip of min� 15 mm to neighbouring objects (e�g�
pipe/tank walls, structures, other LM sensors)
(Fig� 5-1)�
5.2 Installation procedure
5.2.1 Front installation for AF005
► Slide the supplied flat seal over the thread onto the sensor and/or verify its
correct position�
► Slightly grease the thread of the sensor using a lubricating paste which is suita-
ble and approved for the application�
► Screw the sensor into the respective process connection and tighten it�
Max� tightening torque:
► After installation check the tank/pipe for ingress resistance�
26
20���25 Nm
15 mm