Fan unit ELS EC..
– Filter cleaning indicator (Fig.1)
The filter cleaning indicator in the facade indicates the level of contamination of the permanent filter and the
associated reduction in performance via the red check point.
– Filter change (Fig.2-4)
Fig.1
Filter cleaning indicator:
- red
= clean
- white = filter working properly
Fig.3
Pin
Pull!
Release
catch
Remove filter!
Permanent filter
ò
Grille with hinged facade cover – with filter holder and filter cleaning indicator
ù
Place insertion film below the filter for second room connection
ä
Commissioning without a filter is not permitted, as otherwise the unit and entire duct system will be contami-
nated. The functionality of the fire damper may be affected by contamination.
Non-observance will result in a loss of warranty.
All of the following information and instructions are intended for an authorised electrician only!
6.0

Electrical connection

m
The safety instructions specified in section 1.2 must be observed!
The electrical connection must only be carried out by an authorised electrician according to the information in
the enclosed wiring diagrams.
– The relevant standards, safety regulations (e.g. DIN VDE 0100) and the technical connection regulations of the ener-
gy supply companies must be observed!
– An all-pole mains switch/isolator, with at least a 3 mm contact opening (VDE 0700 T1 7.12.2 / EN 60335-1) is man-
datory!
– The network configuration, voltage and frequency must be consistent with the information on the type plate.
Note yellow label on casing!
– The power cable must be introduced so that, in case of water exposure, water entry along the power-supply cable is
impossible. The cable must never be placed over sharp edges.
– The units are protection type IPX5 (jet water-proof ) and correspond to protection class II.
– The electrical connection is carried out at the connection terminals in the casing. The corresponding wiring diagram
for the respective fan type and casing must be observed.
– A control unit parallel to the light is recommended in rooms without windows.
m
The electrical connection must be fully isolated from the mains power supply until final assembly!
Observe wiring diagrams!
Before opening the cover:
After fully isolating the unit and removing the spiral from the casing, wait 3 min. until the connection cover can be ope-
ned.
Fig.2
Fig.4
ò
ù
7
Open facade!
ä
ò
ò
EN