Wireless Room Thermostat (Water Floor Thermostat "Trf1"); Wireless Room Hygrostat (Water Floor Thermostat "Trf1"); Wireless Rf Room Thermostat (High Temperature Circuit Thermostat "Trf2") - Selfio FlowBox-HC Guide D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Wireless room thermostat (Water Floor thermostat "trF1")

5.3.3
With WFHT-RF (BASIC, LCD or MILUX)
If a radio frequency room thermostat is plugged in, the flow temperature calculated on the basis of outdoor
temperature and the curve (= flow temperature preset value) is optimized depending on the main room tempera-
ture.
The offset value is calculated in the following way:
Adjustment = preset value of supplied temperature + (room temperature - actual value) х compen-
sation offset
(Compensation offset:  System parameters: "tr1o" Flow temperature offset for "trF1")
Example 1:
Estimation 1:
Example 2:
Estimation 2:
The pump will be switched off when room temperature will be 1°C upper the setting temperature
of the thermostat.

Wireless room Hygrostat (Water Floor thermostat "trF1")

5.3.4
If a radio frequency room Hygrostat is plugged in, the flow temperature calculated on the basis of outdoor
temperature and the curve (= flow temperature preset value) is optimized depending on the main room
temperature. (See the previous part for more explanation)
The working mode (Heating or Cooling) of the installation could be managed by the end user directly on
the room hygrostat. (See the MILUX humidity leaflet for more explanation)
The residual humidity will be supervised by the MILUX-RF hygrostat in the house. If humidity is detected
the "Wcal" temperature will be increased by step of 0.1°C/minute to avoid a too cold water on the hydraulic
circuit and risk of condensation in the house.

Wireless RF room thermostat (High temperature circuit thermostat "trF2")

5.3.5
If a second circulation pump is installed and managed by the ClimaticControl-HC (Inst:  System param-
eters: installation type, "2P.x"), you can install a second radio frequency room thermostat to supervise the
working of the high temperature pump.
This pump will work in the following way: If the preset room temerature is reached the High water
temperature circulation pump switches off after pump delay time. (PUMP:  System parameters: pump
delay time)
Note: Only a standard room thermostat could be installed on the second circuit.
Ex: WFHT-RF (BASIC, LCD or MILUX).
WFHT-RF BASIC
Only RF thermostats from the WFHT-RF series or the MILUX-RF series can
be used with an active antenna 433,92.
The MILUX-RF Hygrostat can be used only with the 433,92Mhz frequency
RF thermostat initialization to the Controller:
SYSTEM PARAMETERS MENU, section
RADIO-CONFIGURATION with RF room thermostat
preset calculated value of flow temp. = 35 °C; room temperature: preset value = 21 °C,
actual value = 19 °C; offset (tr1o) = 1,5
35 °C + (21 °C – 19 °C) × 1,5K
preset value of flow temperature = 35 °C; room temperature: preset value = 21 °C,
actual value = 22 °C; offset (tr1o) = 1,5
35 °C + (21 °C – 22 °C) × 1,5K
MILUX-RF-xxx
WFHT-RF LCD
=>> flow temperature increased by 3,0K to 38 °C
=>> flow temperature decreased by 1,5K to 33,5 °C