tion is stopped.
HC:
A Heat/Cool switching signal is wired on In-
put1 to manage the working mode of the in-
stallation. (contact between point 2 and In1 or
phase signal on In1)
Heating = no signal (open circuit )
Cooling = Phase signal (closed circuit).
C_b:
A pump signal from a connecting box is wired
on Input1 to manage the working of the
pump1.
(contact between point 2 and In1 or phase
signal on In1)
Heating = no signal (open circuit )
Cooling = Phase signal (closed circuit).
- if "inst"="Act or SEP", water floor Pump1
circulation is stopped & mixing valve is closed.
- if "inst"="2P.x", direct circuit Pump2 circula-
tion is stopped.
_ _ _
OUSE
Outside sensor menu:
Yes: Wired outside sensor is installed.
13
No: Installation without outside sensor
The regulation will work like a "thermostat"
with a adjustable "Wcal" temperature injected
on the circuit.
rF: Wireless RF outside sensor is installed.
The following parameter is only available if no outside sensor is installed and the "OUSE" parameter is set to "no".
_ _ _
OU t
Outside temperature:
This menu is used to fix the outside tempera-
14
ture to have the desired calculated water
temperature in accordance to the curves.
Example:
Ou t = 0°C, Curv = 1
Wcal => 40°C
You could adjust with more accuracy the
"Wcal" temperature since the main screen
with the "Comfort" and "Reduced" offset.
The following parameter is only available if "OUSE" parameter is set to "rF"
RADIO-CONFIGURATION with RF sensor for outdoor temperature
Same radio configuration sequence as parameter 8 "trF1" above.
14
Temperature indication in °C or °F
16
Time indication mode
24 hours or 12 hours
17
Side-track protection
18
When YES is selected the pump and the auxiliary actuator are activated at midday 12 hrs, if they
haven't been active for a period of 24 hours. (12h00: Pump ON 1min, 12h01: Open actuator 2min,
12:03: Close actuator 2min)
Yes
00.0°C
°C
24H
YES (ac-
tive)
19
The HC signal
could be done by a
heat pump.
Check the electri-
cal compatibility
before connection
No, rF
-49.0°C to
50.0°C
°F
12H Am/Pm
NO (inactive)
GB