7.2
Heating & Cooling curves
7.3

Corresponding value for sensors.

To be checked with an ohmmeter with sensor unplugged.
Temperature (°C)
Resistance value (Ohm)
-20°C
-10°C
0°C
10°C
20°C
30°C
8

Technical Data / Materials

Measured temperature accuracy:
Operating temperature:
Flow temperature control range:
Regulation characteristics:
Electrical protection:
Supply voltage:
Outputs:
3-point control:
Sensors:
outside temperature:
supplied temperature:
return temperature:
Software version:
Outside temperature (°C)
~94 k
~54 k
~32 k
~20 k
~12,5 k
~8 k
0,1 °C
0 - 50 °C
0 - 100 °C
Non-linear logarithmic PID control
Intelligent 3-point control (automatic detection of operating point)
Class II – IP 30
230 V (±10%), 50 Hz
pump:
5 A / 250 V relay (L, N, PE)
Cold:
5 A / 250 V relay (L, N, PE)
Heat:
5 A / 250 V relay (L, N, PE)
2 TRIACS => 75 W max.
CTN 10 K at 25 °C (class II, IP55)
CTN 10 K at 25 °C (class I, IP68, no coupling)
CTN 10 K at 25 °C (class I, IP68, no supply)
_.__
(displayed when switched off – STOP
Temperature (°C)
40°C
50°C
60°C
70°C
80°C
mode).
21
Fig. 9
Resistance value (Ohm)
~5,3 k
~3,6 k
~2,5 k
~1,8 k
~1,3 k
GB