4-2-2. Power Sharing Mode
Here the Power Sharing level is set to a 30 Amps while the AC output loads consume a total of 20Amps. This
means that only 30-20 = 10 Amps is left over for charging. With 12VDC battery and 120 VAC, this will result in
a maximum charge current of approx. 100A DC. See Fig. 19.
Note: Max AC Input current (by breaker) is the AC bypass current + the charging current.
:
Fig. 19
Power Sharing Function I
The Power Sharing level can be set by means only remote control locally on the unit. When the total
connected AC load reaches the level of the Power Sharing setting (20A), there will be no power left over to
charge the battery. This means that the charge current of the unit will be reduced to 0A. See Fig. 20.
:
Fig. 20
Power Sharing Function II