82 Technical data and references
Notes:
If stopping by coasting is not acceptable, stop the drive and machinery using the
appropriate stop mode before activating the STO.
The STO function overrides all other functions of the drive.
Wiring
The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum
length of the cabling between the switch and the drive control unit is 300 m (1000 ft). Ground
the shield of the cable at the control unit only.
Validation
EN
To ensure the safe operation of a safety function, a validation test is required. The test must
be carried out by a competent person with adequate expertise and knowledge of the safety
function. The test procedures and report must be documented and signed by this person.
DA
Validation instructions of the STO function can be found in the drive hardware manual.
Technical data
DE
Minimum voltage at IN1 and IN2 to be interpreted as "1": 17 V DC
STO reaction time (shortest detectable break): 1 ms
ES
STO response time: 2 ms (typical), 30 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
FI
Fault reaction time: Fault detection time + 10 ms
STO fault indication (parameter 31.22) delay: < 500 ms
FR
STO warning indication (parameter 31.22) delay: < 1000 ms
Safety integrity level (SIL, EN 62061): 3
IT
Performance level (PL, EN ISO 13849-1): e
The drive STO is a type A safety component as defined in IEC 61508-2.
NL
For the full safety data, exact failure rates and failure modes of the STO function, refer to
the drive hardware manual.