Installation space
Reserve space required to install the indoor unit and
for service work.
Keep 300mm or more for clearance between top plate
of the indoor unit and the ceiling surface.
The transport brackets are provided. Following to the table, remove the brackets according to direction of pipe.
(Left, right, center) (For AP0071H to AP0181H, (left) and (right) transport brackets only are provided.)
Pipe side piping
Parts to be removed
Right side piping
Remove transport bracket (right) only.
Rear side piping
Left side piping
Remove all transport brackets.
REQUIREMENT
After removing of the transport brackets, do not
apply force on the lower cabinet. It is to prevent
deformation and breakage.
Pipe connecting position
<Front view>
Top end of installation plate
Drain pipe
<Bottom view>
Shipping from factory (Left side piping)
All manuals and user guides at all-guides.com
(Including installation plate)
Liquid side
Gas
side
60
Left and
right side piping
110
(Knockout hole)
Gas pipe 440
Liquid pipe 540
Drain pipe 560
300 or more
• Remove the installation plate.
Transport bracket
(Center)
Transport bracket
(Right)
210
Installation plate (Accessory)
77
Refrigerant pipe connecting port
liquid side B
Refrigerant pipe connecting port
gas side A
380
450
480
Model MMK-
AP0071H to AP0121H
AP0151H, AP0181H
AP0241H
4
300 or more
Installation plate
Transport bracket
(Left)
Drain pipe
connecting port
A
B
Ø9.5
Ø6.4
Ø12.7
Ø6.4
Ø15.9
Ø9.5