Hysteresis
The hysteresis is above the defined set point value during cooling (CoL).
During heating (Hot), the hysteresis is below the defined set point value.
Note: This Parameter is not available in this selection because An.2 is swit-
ched off ex-factory.
v
Activating An.2, see Chapter 5.6 „Analog inputs"
This parameter is used to set the actual value for relay K4 or the buzzer
An.1: Analog input 1
An.2: Analog input 2
Here, you can define the behavior of the relay or buzzer, if an error occurs on
the set analog input (probe break or short-circuit).
oFF: Relay is to drop out / buzzer OFF
on: Relay is to be energized / buzzer ON
2013-05-01
All manuals and user guides at all-guides.com
0,0...1,0...500 in °C
or
0,0...1,8...900 in °F
An.1, An.2
oFF, on