5.2 Setting the switching behavior of relay K2
Parameters Meaning
CoL: Cooling
When the set point value and the hysteresis are exceeded, relay K2 is energi-
zed.
When the set point value is gone below, relay K2 drops out.
Hot: Heating
When the set point value is exceeded, relay K2 drops out.
When the set point value and the hysteresis are gone below, relay K2 is ener-
gized.
Set point value for the function
Absolute setting (AbS):
Set point value SP.2 directly affects relay K2 as a temperature absolute
value.
Relative setting (rEL):
Value SP.2 is used dynamically as a hysteresis to set point value SP1.
In this manner, it is possible to set an additional limit value monitoring for
SP.1.
All manuals and user guides at all-guides.com
.
5 Parameter level
Value range
from..factory-setting..to
CoL, Hot
absolute::
-200...0...500°C or
-328...32...932°F
relative:
-500...0...500°C or
-900...0...900°F
AbS, rEL
14
Your
setting