中文
通訊參數
從菜單23進入" modbus"子菜單,以編輯與RS485#2相關的以下參數:
從站地址:從1到254,默認為1
Baud Rate: 9600/19200, default 19200
Parity: NONE
指令
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
參數圖
VARIABLE
ON/OFF
OPERATING SPEED
SETPOINT 1 TEMPERATURE
(SP1) - BYPASS
SETPOINT 2 TEMPERATURE
(SP2) - POSTHEATER
SUPPLY SPEED 1 (V1S)
SUPPLY SPEED 2 (V2S)
SUPPLY SPEED 3 ((V3S)
SUPPLY SPEED 4 ((V4S)
(SE ESISTENTE)
EXHAUST SPEED 1 (V1H)
EXHAUST SPEED 2 (V2H)
EXHAUST SPEED 3 (V3H)
EXHAUST SPEED 4 (V4H)
TIME PERIOD ENABLE
MINIMUM PERMITTED
SPEED (VMIN)
MAXIMUM PERMITTED
SPEED (VMAX)
RELATIVE HUMIDITY HR% 16BIT-INT
AIR QUALITY VOC
TEMPERATURE NTC 1
TEMPERATURE NTC 2 (EST) 16BIT-INT
TEMPERATURE NTC 3
TEMPERATURE NTC 4
ACTIVE BYPASS
ACTIVE NOFROST
ACTIVE POSTHEATER
ALARM PRESENCE
162
All manuals and user guides at all-guides.com
TYPE
PERMITTED VALUES
BOOL
16BIT-INT
1,2,3,4
16BIT-INT
15 ÷ 30
16BIT-INT
10 ÷ 25
16BIT-INT
VMIN ÷ V2S
16BIT-INT
V1S ÷ V3S
16BIT-INT
16BIT-INT
V3S ÷ VMAX
16BIT-INT
VMIN ÷ V2H
16BIT-INT
V1H ÷ V3H
16BIT-INT
V2H ÷ V4H
16BIT-INT
V3H ÷ VMAX
BOOL
TRUE, FALSE
16BIT-INT
0 ÷ VMAX
16BIT-INT
VMIN ÷ 100
0 ÷ 100
16BIT-INT
0 ÷ 100
16BIT-INT
-40 ÷ 60
-40 ÷ 60
16BIT-INT
-40 ÷ 60
16BIT-INT
-40 ÷ 60
BOOL
TRUE,FALSE
BOOL
TRUE,FALSE
BOOL
TRUE,FALSE
16BIT-INT
(*)
READ/WRITE
TRUE, FALSE
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
W/R
R
R
R
R
R
R
R
R
R
R
R
R
ADDRESS
16399
16400
16401
16402
16403
16404
16405
16406
16407
16408
16409
16410
16411
8961
8964
8974
8975
8976
8977
8978
8979
8981
8982
8983
8984