Ecoflam MAXFLAM 10 Données Techniques page 16

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
Start up
- Setting data table - Air regulation
pressure in
burner
combustion
output
chamber
kW
mbar
68
91
108
136
pressure in
burner
combustion
output
chamber
kW
mbar
171
1,2
205
1,5
239
1,8
274
2
308
2,3
342
1
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
B
Maxflam 30
16
www.ecoflam-burners.com
Maxflam 10
nozzle
oil
60°
pump
output
HO
pressure
kg/h
setting
bar
6
1,00
23
8
1,25
23
9,5
1,50
23
12
2,00
21
Maxflam 30
nozzle
oil
60°
pump
output
HO
pressure
kg/h
setting
bar
15
2,50
23
18
3,00
23
21
3,50
23
24
4,00
23
27
4,50
23
30
5,00
23
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
Adjusting the air (A).
To act on the screw in figure:
• Turn the air damper until you reach the
requested value.
B
air
pressure in
firing
burner
damper
combustion
head
output
setting
chamber
kW
1
2,20
108
1
2,80
142
1
3,50
179
2
4,50
227
air
firing
damper
head
setting
1
1,25
2
1,5
2
1,8
3
2
3
2,5
4
3
Maxflam 10-20
1 2 3
Maxflam 20
nozzle
oil
60°
output
HO
pressure
kg/h
mbar
9,5
1,50
12,5
2,00
15,8
2,50
20
3,00
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Firing head setting (B).
Slide the burner out off mounting flange.
Modify air cilynder position (1,2,3,4) as
shown in fig.B using a screwdriver. Slide
again the burner in the mounting flange
end fix to the boiler.
air
firing
pump
damper
head
setting
setting
bar
23
1
3,50
23
2
4,50
23
2
5,50
23
3
8,00
420010602200

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Maxflam 20Maxflam 30

Table des Matières