Upper control air connection
(for SFB and SFI)
Lower control air connection
(for SFA and SFI)
Fig. 7:
Control air connection
orifice
Vs, pp, pVc, pVdF, Vg
(Diaph-
epdm/
ptFe/advanced
ragm
Fkm
ptFe/laminated
size)
advanced ptFe
[mm]
8
2
2.5
15
3.5
20
4
4.5
25
5
32
6
40
8
50
12
65
20
Tab. 2:
Tightening torques for diaphragms
12
All manuals and user guides at all-guides.com
Va and Vp
epdm/
ptFe/advanced
Fkm
ptFe/laminated
advanced ptFe
2.5
2.5
4
3.5
4
4
4.5
6
7
8
8
8
10
10
12
15
15
15
20
30
-
-
english
Type 2030, 2031, 2031 K, 2032,
Assembly
7.3.2
connection of the control medium
control function a:
→
Connect control medium to lower connection.
control function b:
→
Connect control medium to upper connection.
control function i:
→
Connect control medium to upper and lower connections
(see "Fig. 7: Control air connection").
→
Pressure on the upper connection closes the valve.
→
Pressure on the lower connection opens the valve.
7.4 maintenance work
7.4.1
actuator
The actuator of the diaphragm valve is maintenance-free provided it is
used according to these operating instructions.
7.4.2
Wearing parts of the diaphragm valve
Parts which are subject to natural wear:
• Seals
• Diaphragm
→
If leaks occur, replace the particular wearing part with an appro-
priate spare part.
The maintenance and repair instructions can be found in the
internet at: www.burkert.com.
A distended PTFE diaphragm may reduce the flow-rate.
2033, 2037