2. PRODUCT OPERATION

The MODBUS product can be configured in Class A or in Class C.
N.B: Configuring the product in Class C does not change the application behavior of the product but will activate the permanent listening of the
product towards the network. It is therefore necessary for the network to recognize it as a Class C device (specific contract or sensor declared in
Class C).

2.1. Global Operation

FR
Important: adeunis® use the most significant byte first format.
The product has several operating modes:
EN

2.1.1 PARK mode

The product is delivered in PARK mode, it is in standby mode and its consumption is minimal. To switch the product out of the Park* Mode pass
a magnet across it for a duration higher than 6 seconds. The green LED illuminates to indicate the detection of the magnet and then flashes
quickly during the product starting phase.
The device then sends its configuration and data frames.

2.1.2 COMMAND mode

This mode allows the user to configure the registers of the product.
To enter this mode, connect a cable to the micro-USB port of the product and choose to use the IoT Configurator or to use the command mode
by an AT command. The exit of the COMMAND mode can be done with an ATO command or unplugging the USB cable.
The product will turn into the configured mode, PARK or PRODUCTION.

2.1.3 PRODUCTION mode

This mode allows the user to operate the product in its final use.
Command send-
ing by serial link
COMMAND MODE
PARK MODE
Presence of a magnet
on the product >6s
PRODUCTION MODE
Page
34
of 43