THERMOBILE AT 400 Manuel De L'utilisateur page 16

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Fault
The flame is extin-
9
guished immediately
after ignition; the
control light is on.
The air combustion
10 The combustion thermo-
fan keeps running,
while the hot air fan
has stopped and the
heater has cooled
down.
There is soot forma-
11
tion in the combus-
tion chamber and in
the flue.
There is soot forma-
12 There is insufficient sup-
tion in the combus-
tion chamber and in
the flue.
13 The flue draught is too
There is leakage
14 There is leakage
between the bottom
of the control panel
and the vaporiser.
The flame goes out
15 The flue draught is too
directly after ignition.
16
All manuals and user guides at all-guides.com
Cause
There is no proper flue
draught.
stat is defective.
The combustion air fan
is not functioning.
ply of combustion air
high or irregular.
between the bottom of
the control panel and
the vaporiser.
low.
40.020.943 - rev. 04 - 2011
Solution
Check whether the flue is fit-
ted according to the descrip-
tion, see "flue".
Check the flue for leakage.
Clean the flue if necessary.
See faults: 3 and 4.
Replace the combustion
thermostat.
Check the motor and replace
if necessary.
Clean the holes in the vapor-
iser.
Check the functioning of the
combustion air fan.
Position a flue stack valve,
see "flue".
Adjust the flue to the right
pressure, see § 5.3.
See faults: 9, 12, and 13.
Adjust the pressure on the
seal cord.
Replace the seal cord.
Check all connections in the
flue.
Check whether the draught
regulator is off.
Check the flue for blockage.
Reduce the number of
bends.
Heighten the flue.
AT 400 - 500-US series
Action
User
User
User
User
Dealer
User
User
Dealer
User
User
User
User
User
User
User