Toshiba RAV-SP404AT-E Manuel D'installation page 7

Climatiseur (type split)
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Super Digital Inverter
Refrigerant Piping
New refrigerant (R410A)
When using the conventional piping
When using the conventional piping with no indication of applicable refrigerant types, be sure to use it with a wall thickness
of 0.8 mm for Ø6.4 mm and Ø12.7 mm. Do not use the conventional piping kit with a wall thickness less than these
thicknesses due to insufficient pressure capacity.
When using general copper pipes
Use general copper pipes with a wall thickness of 0.8 mm for Ø6.4 mm and Ø12.7 mm.
Do not use any copper pipes with a wall thickness less than these thicknesses.
Flare nuts and flare machining
The flare nuts and flare machining are different from those for the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or those for R410A.
Before performing flare machining, carefully read "REFRIGERANT PIPING".
6
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières