Toshiba RAV-SP404AT-E Manuel D'installation page 19

Climatiseur (type split)
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Super Digital Inverter
How to wire
1. Connect the connecting wire to the terminal as identified
with their respective numbers on the terminal block of the
indoor and outdoor units.
H07 RN-F or 60245 IEC 66 (1.5 mm
2. When connecting the connecting wire to the outdoor unit
terminal, prevent water from coming into the outdoor unit.
3. Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they do
not touch any electrical or metal parts.
4. For interconnecting wires, do not use a wire joined to
another on the way.
Use wires long enough to cover the entire length.
Screw
Connecting wire
Stripping length power cord and connecting wire
10
1 2 3
40
Earth line
Connecting wire
2
or more)
Terminal block
1
2
3
L
N
Power wire
10
L N
10
10
40
30
30
Earth line
(mm)
Power wire
CAUTION
An installation fuse must be used for the power supply
line of this air conditioner.
Incorrect/incomplete wiring may lead to an electrical fire
or smoke.
Prepare an exclusive power supply for the air conditioner.
This product can be connected to the mains power.
Fixed wire connections :
A switch that disconnects all poles and has a contact
separation of at least 3 mm must be incorporated in the
fixed wiring.
18
EN

Publicité

Chapitres

Table des Matières
loading

Table des Matières