NORDAC ON / ON+ (SK 3xxP) – Manuel avec instructions de montage
Frame
Size
all
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 DC Symmetrical Amperes, 410 Volts
(-123 Devices) or 715 Volts (-340 Devices) Max., When Protected by R/C Semiconductor fuses, type______,
manufactured by _____", as listed in
all
"Suitable For Use On A Circuit Capable Of Delivering Not More Than ______ rms Symmetrical Amperes, 240 (1-
phase) or 480 (3-phase) Volts Max., When Protected by High-Interrupting Capacity, Current Limiting Class
____Fuses or faster, rated ______Amperes, and ____Volts", as listed in
all
"Suitable for Use On A Circuit Capable Of Delivering Not More Than _______ rms Symmetrical Amperes, ____
Volt maximum" (240V for 1-phase models or 480V for 3-phase models),
"When Protected by Circuit Breaker (inverse time trip type) in accordance with UL 489, rated ______ Amperes,
and _______Volts", as listed in
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class RK5 Fuses or faster, rated max. 15 Amperes.
3
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class RK5 Fuses or faster, rated max. 30 Amperes".
1
"Suitable for motor group installation on a circuit capable of delivering not more than 20000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by High-Interrupting Capacity, Current Limiting
Class J Fuses or faster, rated max. 15 Amperes".
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 15 Amperes and respectively 240 or 480 Volts min.".
3
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 30 Amperes and respectively 240 or 480 Volts min.".
1
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, DC 715 V max, when Protected by 50 215 26 from SIBA rated max. 20 Amperes"
1)
7.2.1 "Caractéristiques électriques 3~ 400 V"
Pos : 57 /Allgem ein/Allgem eing ültige M odul e/---------Seitenum bruc h k om pak t --------- @ 13\mod_1476369695906_0.docx @ 2265500 @ @ 1
20
description
1)
1)
1)
BU 0800 fr-0822