Wiring; Wiring The Kapiris Iii; Maximum Length Of 12V Dc Power Supply Cables - SORHEA KAPIRIS III Notice D'installation

Detecteur bi-technologie
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SORHEA
6

WIRING

6.1 Wiring the KAPIRIS III

*If the 2 switches are raised then the tamper (AP) contact is handled through outputs 13 and 14.
Otherwise, if the 2 switches are lowered then the tamper contact is networked to be rerouted on the
MAXIBUS III hub.
Tamper contact on the sensor

6.2 Maximum length of 12V dc power supply cables

(Wire type SYT1 shielded)
 wire
(mm)
Note: When using the same cable to supply power to several components, the indicated distances
should be divided by the number of connected components.
When using several wires with the same section in parallel by polarity, the indicated
distances should be multiplied by the number of connected wires.
Switches up
Wire section
2
(mm
)
0.6
0.3
0.9
0.6
1.4
1.5
1: 12V dc power
2: 0V dc power
3: A bus RS485
4: B bus RS485
5: A bus RS485
6: B bus RS485
7: Intrusion alarm contact NO
8: Intrusion alarm contact COM
9: Anti-masking alarm contact NO
10: Anti-masking alarm contact COM
11: Auxiliary input +
12: Auxiliary input -
13: Tamper (AP) contact*
14: Tamper (AP) contact*
Switches down
Tamper contact on the network
KAPIRIS III
Maximum length of cables (in meters)
Ethernet enabled
125
281
627
- 36 -
Ethernet not enabled
58
130
289
KAPIRIS III