Using the IAQPoint
Programming Menus
Setting the BACNet ID
This option is only available if the communication type ("Set Comm IF"
menu) for the device is BACNet and should only be configured by
qualified personnel. It allows users to program a specific MAC ID for
the device.
Use the Up or Down buttons to increase or decrease the value to
the desired ID and press Enter to confirm.
Note: The MAC ID must be unique. Selecting an ID that is already in
use may cause network conflicts.
The screen returns to the main menu option.
Setting the Baud Rate
This option let you select from a list of possible baud rates for the active
communication type.
Scroll to the Set Baud Rate screen and press Enter to select.
Use the up or down buttons to display the desired baud rate (available
rates are: 4800, 9600, 38400, 57600).
Note: the baud rate for a connection to a 301C is always 9600. The
usual baud rate is 9600 for BACNet communication and 4800 for
FLN communication.
24
All manuals and user guides at all-guides.com
* Menu *
Set BACNet ID
Set BACNet ID
1
* Menu *
Set Baud Rate.
Set Baud Rate
4600
IAQPoint User Manual
Honeywell
511838
11/07