Honeywell IAQPoint Manuel D'utilisateur page 17

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

All manuals and user guides at all-guides.com
7. Connect the power and outputs as shown in the Wiring Details on
page 16.
8. Press the IAQPoint onto the plastic base (latches will click), making
certain that sampling tube feeds into the appropriate port on the
back of the IAQPoint.
Note: Honeywell uses ft/minute velocity rules, however other industries or
companies use CFM: To convert from CFM to velocity (ft/minute), divide
the flow by the area (Example: In a 2 ft x 4 ft duct, where the area is 8 sq.
ft with a CFM of 30,000, the air velocity will be 30,000 cu. ft/minute/(8 sq.
f
) = 3,750 ft/minute)
t
511838
11/07
IAQPoint User Manual
Honeywell
Introduction
Installation Instructions
15

Publicité

Chapitres

Table des Matières
loading

Table des Matières