1. GENERAL
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set of
instructions for the indoor units and make sure all accessory
parts listed are with the indoor units before beginning.
1-1. Tools Required for Installation (not supplied)
1.
Flathead screwdriver
2.
Phillips head screwdriver
3.
Knife or wire stripper
4.
Tape measure
5.
Carpenter's level
6.
Sabre saw or keyhole saw
7.
Hacksaw
8.
Core bits
9.
Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
No.
Accessories part
Installation plate
1
Installation plate fixing screw
2
Installation Instruction
3
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing.
Cut each tube to the appropriate lengths +30 cm to 40 cm
to dampen vibration between units.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3.
Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
Refer to 4. ELECTRICAL WIRING for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.
1-4. Additional Materials Required for Installation
1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire (See your
local codes.)
3.
Putty
4.
Refrigeration tubing lubricant
5.
Clamps or saddles to secure refrigerant tubing
6.
Scale for weighing

2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of the
room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
WARNING
Qty.
select a location which can support a load that is four times
1
the indoor unit weight.
5
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
1
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
instructions packed with the outdoor unit.
allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight nor in the
flow of cool air from the indoor unit.
N OT E
Air delivery will be degraded if the distance from the floor to the
ceiling is greater than 3 m.
The air inlet and outlet of the indoor unit must be free of any
obstructions to allow air to spread throughout the room.
1.
The indoor unit must be within a maintenance space.
100 or more
6
Wall Mounted
(Unit: mm)
50 or more
Front View
Fig. 2-1