63A single-phase energy meter,
MID direct connection

9. COMMUNICATION

RS485 Modbus wiring diagram:
IF4E011/SXIIP
ETHERNET
RJ45
(3)
RS485 Modbus wiring diagram with Mini Web Server:
3
RS485: Required use of Belden 9842 or Belden 3106A wire (or equivalent) for a maximum bus length of 1000 m, or Category 6 wire
(1)
(FTP or UTP) for a maximum length of 50 m
120Ω terminating resistor inside the instrument (it can be set in the SETUP menu)
(2)
Ethernet: Cat. 6 (FTP/UTP)
(3)
Mbus wiring diagram:
MASTER
MBUS
Communication tables
- The MODBUS and MBUS communication protocols are available on the
Technical data sheet: IDP000193EN_06
CE2DF3.....
RS-485
+ – SG
+ – SG
SXWS10/SXWS32
RS-485
+ – SG
MBUS
A B
(5)
Non-polarized connections
A two-wire standard telephone cable (JYStY N*2*0.8 mm)
(5)
Updated: 13/04/2021
Codes: CE2DF30PMID – CE2DF3DTMID – CE2DF3MTMID
Model: CONTO D2
CE2DF3.....
N°1
N°2
+ – SG
CE2DF3.....
CE2DF3.....
N°1
N°2
+ – SG
+ – SG
MBUS
A B
http://www.imeitaly.com,
CE2DF3.....
N°n
+ – SG
CE2DF3.....
N°n
+ – SG
MBUS
A B