ASTRALPOOL CDP LINE V2
4.4.
CONDENSATION DRAINAGE
Carefully plan for an appropriate water drainage slope to ensure a smooth water flow. Drainage
shall be made via a siphon.
The water drainage consist of a translucent rubber hose (20x1, 5mm) and is located on the
lower right side of the machine. See IMAGE 1 (page 85) for more detailed location and
dimensions.
4.5.
ELECTRICAL CONNECTION
The power supply for the unit must be, preferably, from a sole circuit and provided with
standard-issue protection components: protection by a 30 mA differential and a magnetic
circuit breaker. See IMAGE 5 (pg. 89).
The electrical installation must be carried out by a qualified professional (an electrician, for example)
according to the applicable laws and regulations of the target country.
The dehumidifier circuit must be linked to a safety earth circuit levelled to the terminal
block.
The cables must be correctly installed so that they do not cause interferences (items in
the lead boards).
The unit must be connected to an earthed 230/50Hz/I+N general-purpose power
supply.
TABLE 2 (pg. 77), shows some indicative cable sections, which must be verified and
adapted according to the installation needs and conditions and always following
regional and country regulations.
All wiring should comply with local and national electric codes and should not be prone
to overheating and subsequent voltage failures. As a guide, you can use the general
power supply table for lengths of less than 25 metres.
The acceptable tolerance to voltage fluctuation is +/- 10% during operation.
Connect the equipment following the wiring diagram included in this manual.
Place a U-curve thermal-magnetic circuit breaker in the general power connection to
protect the line in the case of a short in the circuit.
Place a differential circuit breaker in the general power connection to protect the
equipment from possible grounding problems. The differential breaker should be
minimum 30 mA.
Before installing the connections, be sure to disconnect the electricity so that the
power supply is turned off.
Connect the power supply wires to the unit's input terminal.
Connect the grounding wire to its corresponding terminal.
All local and national electricity codes concerning the protection of defects in electric power
lines should be respected at all times during the electrical installation.
Verify the torque of all electrical connections.
The electrical resistance between the ground and any electric terminal will be verified to be
over 1 megaohm. Otherwise, the equipment will not start up until electrical loss is located and
repaired.
In the case of fluctuations in the power supply, a power supply stabilising system is
recommended in order to protect the equipment.