OPERATION
• Automatic open and closing with hand presence detection. For the mains supply models, shut-off
is automatic in the event of electrical failure.
• Anti-blocking safety: a safety time flow guarantees shut-off after 30 seconds of flow, in the event
of negligence or an obstacle in the detection area. Once the obstacle is removed, operation will restart
automatically (Fig.S1, S2).
• Anti-bacterial proliferation duty flush: automatic flush ~60 seconds every 24 hours after the last use
(can be adjusted to 12h or deactivated): place the pin connectors facing the desired programme (Fig.Q).
For all UK specific references the default setting for the duty flush feature is OFF.
ELECTRICAL SUPPLY
IP65 waterproof electronic housing.
For mains supply models:
• Electrical supply 100-240V / 50-60Hz class II TBTS SELV (separated from earth).
• The installation must conform to local Electrical Regulations/Standards and must be installed by
a competent, qualified electrician.
• If the supply cable is damaged, the installer must replace it.
• Secure the cables in place with a fixed router e.g. a rigid sheath or cable holder.
For battery-operated models:
• Electrical supply with two 3V Lithium batteries, supplied in the box.
• In order to preserve the batteries, room temperature must be ≥ 5°C.
INSTALLATION
• Tap: supply with cold or mixed water.
• Mixer: supply with cold and hot water up to 60°C maximum (we recommend 45°C to avoid the risk
of scalding) balancing the pressure (ΔP < 1 bar).
• The filter seals supplied must be fitted. Do not fit additional seals.
• Pressure: 1 bar (100 kPa) to 5 bar (500 kPa), recommended 3 bar (300 kPa). Pressure difference
at inlets: 1 bar maximum.
• To avoid interference with infrared rays, do not install two electronic taps/mixers facing each other
or bright objects.
Installing the spout (for the TEMPOMATIC PRO):
• Remove the white plastic cap and place the spout onto the tap/mixer and tighten it. The spouts can
turn 360°.
REMEMBER
• Our mixers/taps must be installed by professional installers in accordance with current
regulations and recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer (see
calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce the
frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the mixer/tap to facilitate maintenance.
• The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings should
be checked at least once a year, and more frequently if necessary.