Power supply
12.3 Sensor installation
12.3.1 Outside temperature sensor AFS 2
The outside temperature sensors have a significant influence on
the function of your heating system. Therefore ensure that the
outside temperature sensors are correctly positioned and well
insulated.
- Install the outside temperature sensor on a north or
north-eastern wall.
- Ensure that the outside temperature sensor is freely exposed
to the elements but not placed in direct sunlight.
- Never mount the outside temperature sensor above win-
dows, doors or air ducts.
- Observe the following minimum clearances: 2.5 m above the
ground and 1 m to the side of windows and doors
Installation
f Remove the cover.
f
f Secure the base with the screw supplied.
f
f Connect the cable. Connect the outside temperature sensor to
f
T(A) of terminal X2.2 of the appliance.
f Replace the cover. The cover must audibly click into place.
f
44
| HSBC
319204_HSBC_200_de_en_fr_nl_it.indb 44
12.3.2 Fitting the temperature sensor (accessory) for area
cooling
Area cooling requires the fitting of a temperature sensor, available
as an accessory.
f Remove the front casing (see chapter "Preparations / Trans-
f
port and handling / Removing / fitting the front casing").
f Insert the temperature sensor into the sensor well "Sensor
f
heat pump cooling, optional".
f Connect the temperature sensor to T(Kue/WW) of termi-
f
nal X2.1 of the appliance.