How to connect wiring to the terminal

■ For stranded wiring

(1) Cut the wire end with cutting pliers,
then strip the insulation to expose
the stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 4-7)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal board.
(3) Using a ring connector fastener or
pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal,
and replace and tighten the removed
terminal screw using a screwdriver.
(Fig. 4-8)

■ Examples of shielded wires

(1) Remove cable coat not to scratch braided shield. (Fig. 4-9)
(2) Unbraid the braided shield carefully and twist the
unbraided shielded wires tightly together. Insulate the
shielded wires by covering them with an insulation tube or
wrapping insulation tape around them. (Fig. 4-10)
(3) Remove coat of signal wire. (Fig. 4-11)
(4) Attach ring pressure terminals to the signal wires and the
shielded wires insulated in Step (2). (Fig. 4-12)
■ Wiring samples
Stranded wire
Ring
pressure
terminal
Fig. 4-7
Functional ground screw
(Louver Motor)
Use this screw when
connecting the shield
for the inter-unit control
wiring to ground
11
Special
Screw
washer
Ring pressure
terminal
Terminal board
Wire
Wire
Fig. 4-8
Fig. 4-9
Insulation tape
Fig. 4-10
Insulation tape
Fig. 4-11
Fig. 4-12
Functional ground screw
(Schedule Timer)
Protective ground screw
(External Solenoid Valve
Kit for 3WAY)
Power supply cord
Screw and
Special washer
Ring
pressure
terminal
Shield mesh
Shield mesh
Remote
control wiring
Inter-unit
control wiring

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières