8 Setting the limit contacts
16
TP8
Potentiometer for switch-off delay of GK2
Setting range: 0—10 sec
J1
Jumper for switching point of GK1 in the positive / negative
pressure ranges (for ± ranges)
1
2
3
1
2
3
J2
Jumper for switching point of GK2 in the positive / negative
pressure ranges (for ± ranges)
1
2
3
1
2
3
J3
Jumper for relay function of GK1
1
2
3
1
2
3
J4
Jumper for relay function of GK2
Bridge 1-2 => GK1 switches in the positive
pressure range
Bridge 2-3 => GK1 switches in the negative
pressure range
Bridge 1-2 => GK2 switches in the positive
pressure range
Bridge 2-3 => GK2 switches in the negative
pressure range
Bridge 1-2 => GK1 = min. limit contact
Bridge 2-3 => GK1 = max. limit contact
Bridge 1-2 => GK2 = min. limit contact
Bridge 2-3 => GK2 = max. limit contact