JUMO 404304 Mode D'emploi page 35

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Required
aids
Controls
Description
Rating of limit contact: 6 A max. at 230 VAC
- pressure generator
- supply for pressure/differential pressure transmitter
- reference pressure measuring device or voltmeter/ammeter (multimeter)
TP1
TP2
GK1
J1
J2
TP5
TP6
ST5
TP1
Potentiometer for limit of limit contact 1 (GK1)
Setting range: 0—100% of full scale
TP2
Potentiometer for hysteresis of GK1
Setting range: 1— 99% of full scale
TP3
Potentiometer for switch-on delay of GK1
Setting range: 0—10 sec
TP4
Potentiometer for switch-off delay of GK1
Setting range: 0—10 sec
TP5
Potentiometer for limit of limit contact 2 (GK2)
Setting range: 0—100% of full scale
TP6
Potentiometer for hysteresis of GK2
Setting range: 1—99% of full scale
TP7
Potentiometer for switch-off delay of GK2
Setting range: 0—10 sec
8 Setting the limit contacts
TP3 TP4
ST4
GK2
J4
TP7 TP8
J3
5 6 7
8 9 10
15