Troubleshooting - Generac XD5000E Manuel Du Propriétaire

Masquer les pouces Voir aussi pour XD5000E:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

NOTE: Always treat diesel fuel for long
term storage. Use the approved fuel addi-
tive and water abatement material. Test
stored fuel every 90 days and provide addi-
tional treatment if required. Periodically
check and dry abatement material as nec-
essary.
Change Oil
Change engine oil before storage. See
"Change Engine Oil."

Troubleshooting

PROBLEM
Engine is running, but
AC output is not
available.
Engine runs well at
no-load, but bogs when
load is applied.
Engine will not start; or
starts and runs rough.
Operator's Manual for Portable Generator
CAUSE
1. Circuit breaker OPEN.
2. Poor connection or defective
cord set.
3. Connected device is bad.
4. Fault in generator.
5. Main breaker switch is OFF.
6. Voltage selector switch is OFF.
7. Generator is overloaded.
8. GFCI outlet has tripped.
1. Short circuit in a connected
load.
2. Generator is overloaded.
3. Engine speed is too slow.
4. Shorted generator circuit.
1. Incorrect start sequence.
2. Fuel valve is OFF.
3. Dirty air filter.
4. Out of fuel.
5. Stale or contaminated fuel.
6. Low oil level.
7. Excessive rich fuel mixture.
8. Dirty fuel filter.
9. Air in fuel system.
10. Engine is under electrical load.
Return Engine to Service
1. Refer to the
"Before Starting Engine."
section.
2. Start engine and run at no load for 5 to 10
minutes while checking:
• oil pressure
• fuel, engine oil or coolant leaks
• proper operation of indicators/gauges
NOTE: Avoid prolonged operation at mini-
mum or maximum engine speeds and
loads for the first hour of operation.
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is
in good condition.
4. Contact Authorized Service
Facility.
5. Switch main breaker ON.
6. Switch voltage selector switch
to desired voltage output.
7. See
its."
8. Correct ground fault in circuit
and reset GFCI.
1. Disconnect shorted electrical
load.
2. See
its."
3. Contact Authorized Service
Facility.
4. Contact Authorized Service
Facility.
1. Review & follow starting pro-
cedure.
2. Turn fuel valve ON.
3. Clean or replace air filter.
4. Fill fuel tank.
5. Drain fuel tank and fill with
fresh fuel.
6. Fill crankcase to correct level.
7. Contact Authorized Service
Facility.
8. Replace fuel filter.
9. Contact Authorized Service
Facility.
10. Remove all equipment from
receptacles. Make sure the
main breaker switch is OFF.
CORRECTION
"Know Generator Lim-
"Know Generator Lim-
17

Publicité