P6 Menu - Serial Communication - LEGRAND 261 93 Mode D'emploi

Masquer les pouces Voir aussi pour 261 93:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Programmable output functions
Function
OFF
S.GE
RDY
ALA
MCM
MCS
L.SH

7.9 P6 menu - Serial communication

Setup
P6.01
The highlighted
parameters are
P6.02
included only in
version 261 94
P6.03
P6.04
P6.05
P6.06
P6.07
P6.08
P6.01...P6.04 - They determine the transmission format and the protocol used on communication port RS-232
P6.05...P6.08 - They determine the transmission format and the protocol used on communication port RS-485,
Description
OFF
Consent to start up the generator
Automatic transfer switch ready
Global alarm
Minimum coil
Main line
Minimum coil
Secondary line
Non-priority load disconnection
Description
Serial address RS-232
Speed (baudrate) RS-232
Protocol RS-232
Parity RS-232
Serial address RS-485
Speed (baudrate) RS-485
Protocol RS-485
Parity RS-485
available only on 261 94
Notes
Output not used
When closed, the generator must be inactive.
Contact opens to start generator.
If the unit is not powered, the generator starts
Indicates unit automatically and without alarms, ready to
start operating
De-energizes in case of an alarm
Main line switch voltage minimum opening coil command
Secondary line switch voltage minimum opening coil
command
Disconnection of the non-priority loads that are not powered
by the secondary line branch.
It is also controlled on the secondary line.
Contact which is closed before the secondary line closing
command and opened before the main line closing
command
Range
1...245
240 = 2400
480 = 4800
960 = 9600
19.2 = 19200
38.4 = 38400
Rtu = Modbus RTU
ASC = Modbus ASCII
No = None
EVE = Even
Odd = Odd
1...245
240 = 2400
480 = 4800
960 = 9600
19.2 = 19200
38.4 = 38400
Rtu = Modbus RTU
ASC = Modbus ASCII
No = None
EVE = Even
Odd = Odd
Default
01
960
RTU
No
01
960
RTU
No
21