Change parameters and save
Ÿ The parameters can be changed when the controller is enabled.
- The parameter sets (C002) can only be overwritten if the controller is inhibited.
Ÿ Changes of the operating parameters are accepted ONLINE.
Ÿ Changes affecting the controller initialization must be confirmed with SH + PRG.
without cofirmation
(ONLINE)
A
1. Operating level ¡ [PRG] ¡ Code level
2. [ L ] or [ M ] ¡ Code selection
3. [SH] ¡ Parameter set PAR1 ( ¡ [SH] ¡ Parameter set PAR2)
4.
4. When PAR1 ( PAR2) is flashing: [ L ] or [ M ] ¡ Change parameters
Frequency immediately
operates with the changed
parameter.
5. [SH]
5. [SH] ¡ Code level
Code level
6. [PRG] ¡ Operating level (changed parameter is saved non-volatile)
B
Parameter sets transmitted
You can transmit complete parameter sets to frequency inverters of the same series
(820X ® 820X, 821X ® 821X, 822X/824X®822X/824X) using the operating module.
to the operating module
1. Operating level ¡ [STP] ¡ Controller inhibited
2. Operating level ¡ [PRG] ¡ Code level
3. [ L ] or [ M ] ¡ Select C002
4. [SH] ¡ PAR1 is flashing ¡ [ L ] or
[ M ] ¡ C002 = -6-
[SH] + [PRG] ¡ Display "STO" until transmission is completed ¡ Code level
The parameters of C016, C036, C088, C091, C079 are not transmitted.
5. [PRG] ¡ Operating level (parameter sets saved non-volatile)
6. [RUN] ¡ Controller enabled
l
Parameters
Acceptance and saving
confirmed with SH +
PRG
[SH] + [PRG] ¡ Display "STO" ( approx. 1 s) ¡ Code level
Frequency inverter now
uses the new
parameter.
Transmit parameter sets
to the frequency inverter
[SH] ¡ PAR1 flashing ¡ [ L ] or [ M ] ¡
C002 = -3- ¡ Transmit PAR1 and PAR2
C002 = -4- ¡ Transmit PAR1
C002 = -5- ¡ Transmit PAR2
- 4 -
confirmed with SH + PRG when
controller is inhibited
Operating level ¡ [STP] ¡ controller
inhibited
[RUN] ¡ Controller enabled
Frequency inverter now uses the
changed parameter.
MA8201BB 2.0