Stop!
Dangerously high temperatures
The filter is not protected against mains phase failure. In the event
of a mains phase failure, the filter may become very hot.
Possible consequences:
ƒ
ƒ
Protective measures:
ƒ
ƒ
O
Warnings!
Conditions of Acceptability:
ƒ
ƒ
ƒ
ƒ
ƒ
EDK84AZESxx DE/EN/FR/ES/IT 5.0
Destruction of the device.
Smouldering or open fire.
Change the setting for code C00565 from "Warning" to "Fault" or
select a wiring for the bMctrlMainsFault status output
(LS_DeviceMonitor) system block which causes the system to
shutdown within one minute if said output is set to HIGH.
These devices shall be used within their Recognized ratings as
described in the ratings section.
The suitability of the mounting means is to be determined in the
end use application.
These devices have been evaluated for factory wiring only.
These devices have been investigated for use in a Pollution
Degree 2 environment.
These devices are to be installed in a suitable end−product
enclosure.