Reconnection
Reconnection Time
Reconnection Time adjustable
F
reconnect value
max
F
reconnect value
min
U
reconnect value
min
U
reconnect value
max
F
reconnect value adjustable
min
F
reconnect value adjustable
max
U
reconnect value adjustable
min
U
reconnect value adjustable
max
U
AC Voltage
AC
[s]
Unit: Seconds
[cyl]
Unit: Cycles (1)
U
U Inner Limit min (min. inner limit voltage)
Imin
U
U Inner Limit max (max. inner limit voltage)
Imax
U
U Outer Limit min (min. outer limit voltage)
Omin
U
U Outer Limit max (max. outer limit voltage)
Omax
U
nominal Voltage
nom
F
F Inner Limit min (min. inner limit frequency)
Imin
F
F Inner Limit max (max. inner limit frequency)
Imax
F
F Outer Limit min (min. outer limit frequency)
Omin
F
F Outer Limit max (max. outer limit frequency)
Omax
default set values:
U < 50%, 50 ≤ U < 88 %, 110 < U < 120 %, U ≥ 120 %, F
reconnection time
The field adjustable trip points can be set at the PROFI Service Menu. The access code will be provided by Fro-
nius upon request.
300 s
5 - 900 s
< 60.5 Hz
> 59.3 Hz
U > 88 %
U < 106 %
45.00 - 65.00 Hz
45.00 - 65.00 Hz
U > 50 % - U > 95 %
U < 101% - U < 120%
+0.5, F
Imax
+ 2.0, F
- 0.7, F
Omax
Imin
- 3.0,
Omin
55