Communication - LEGRAND IME NEMO D4-ec Mode D'emploi

Masquer les pouces Voir aussi pour IME NEMO D4-ec:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Three-phase multifunction instrument
with 1 or 2 "Easy Connect" inputs

9. COMMUNICATION

RS485 Modbus wiring diagram:
ETHERNET
RJ45
RS485 Modbus wiring diagram with Mini Web Server:
3
RS485: Required use of Belden 9842 or Belden 3106A wire (or equivalent) for a maximum bus length of 1000 m, or Category 6 wire
(1)
(FTP or UTP) for a maximum length of 50 m
120Ω terminating resistor inside the instrument
(2)
Ethernet: Cat. 6 (FTP/UTP)
(3)
The "SG" terminal must not be connected to the earth
(4)
Mbus wiring diagram:
MASTER
MBUS
Communication tables:
- The MODBUS and MBUS communication protocols are available on the
Technical data sheet: IDP000348EN_01
SXIIP
RT
RS-485
120 Ω
+
-
SG
(2)
(1)
SXWS10/SXWS32
RS-485
+
– SG
(1)
MBUS
A B
(5)
Non-polarized connections
A two-wire standard telephone cable (JYStY N*2*0.8 mm)
(5)
Codes: MFD41ORFCDT – MFD42ORFCDT
MFD41ORFCMT – MFD42ORFCMT
Model: NEMO D4-ec
IN
OUT
IN
RS485
MFD4...
N°1
IN
OUT
IN
RS485
MFD4...
MFD4...
N°1
MBUS
A B
http://www.imeitaly.com
Updated: -
OUT
IN
RS485
RS485
MFD4...
MFD4...
N°2
OUT
IN
OUT
RS485
RS485
MFD4...
N°2
N°n
MBUS
A B
site
Created: 19/02/2021
SG
+
1
1
+
SG
OUT
RT
120 Ω
N°n
(2)
RT
120 Ω
(2)
7 / 7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mfd41orfcdtMfd42orfcdtMfd41orfcmtMfd42orfcmt

Table des Matières