DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying
this device before working on this device.
15
Operation States [ Estado operatión ]
Definitions / Definiciónes
I
Rated Current / Intensidad asignada
n
I
Cointinuous Amps / Amperios continuo
r
t
Long Time Delay / Retardo largo
r
I
Short Time Pickup / Tiempo corto inicio
sd
LCD Display
[ Pantalla LCD ]
A = XXXX B = XXXX
C = XXXX N = XXXX
Phase X
Overload
WARNING !!!
INVALID COM
TRIP UNIT
MEMORY ERROR
TRIP UNIT
EEPROM ERROR
TRIP UNIT
OVER TEMPERATURE
* In event of damage to the device, Electronic Trip Units are equipped with a Minimum Setting feature. All settings override to the lowest possible value and
the device must be replaced.
[* En caso de daño al aparato, la unidad de disparo esta equipada con una característica de Ajuste de Minimo. Todos los ajuste se convierte al valor mas bajo
posible y la unidad debe ser remplazada. ]
7 / 10
PELIGRO
!
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Desconectar la alimentación eléctrica antes
de trabajar en el equipo.
3ZW1012-OVL02-2AA0
System Status
[ Estado de sistema ]
< 25% x /
n
> 25% x /
n
≥ 25% x /
n
< 105% x /
r
≥ 25% x /
n
> 105% x /
r
> 25% x /
n
Wrong COM2x release connected;
Connect "COM2x Release 2" (or newer)
> 25% x /
n
> 25% x /
n
> 25% x /
n
Option:
16b
Opción:
max. 1.57" [ 4cm ]
t
Short Time Delay / Retardo corto
sd
I
Instantaneous Pickup / Instantánea inicio
i
I
Ground Fault Pickup / Inicio de falla a tierra
g
t
Ground Fault Delay / Retardo de falla a tierra
g
Operational State
[ Estado de operación ]
Contact Technical Support
[ Lamar a Soporte Técnico ]
http://www.siemens.com/lowvoltage/technical-support
May Not Be Operated, Last Selected Settings
*Minimum Settings
[ * Ajuste de Minimo ]
Contact Technical Support
[ Lamar a Soporte Técnico ]
http://www.siemens.com/lowvoltage/technical-support
Contact Technical Support
[ Lamar a Soporte Técnico ]
http://www.siemens.com/lowvoltage/technical-support
Contact Technical Support
[ Lamar a Soporte Técnico ]
http://www.siemens.com/lowvoltage/technical-support
DANGER
!
Tension électrique.
Danger de mort ou risque de blessures graves.
Mettre hors tension avant d'intervenir sur
l'appareil.
16a
1
3
OK
Not OK
OK
OK
Not OK
Not OK
Bestell-Nr. / Order No.: 3ZW1012-0VL02-0AA0