NOTE
Power reduction due to heat accumulation!
If the recommended minimum clearances are not observed, the device may go into power regulation
mode due to insufficient ventilation and the resulting heat build-up.
Observe minimum clearances and provide for sufficient heat dissipation.
All objects on the device housing must be removed during operation.
Ensure that no foreign bodies prevent heat dissipation following device installation.
Lifting and installing the device
↻ The mount has been installed.
1 Lift the device using the side recesses. Observe the device's centre of gravity!
NOTE: Do not lift the device by the lid or cover!
2 Suspend the device in the mount using the recess on the rear of the device. ( [See figure 8] [} Page 16]).
NOTE: Keep in mind that the lower marking on the housing must protrude over the upper outer contour of the
mount. Ensure that the upper marking is flush with the upper edge of the outer contour when lowering the device.
The outer contour of the mount must be flush with the outer contour of the housing.
3 Insert the screw provided into the lug of the mount and secure the device to prevent it from being lifted off [ T30 /
2 Nm]. ( [See figure 7] [} Page 16]).
NOTE: Alternatively: At this point, the screw described above can be replaced by a special screw as anti-theft pro-
tection.
» Device is installed. Proceed with the electrical installation.
CAUTION
Property damage as a result of condensation
During pre-assembly of the devices, moisture can penetrate into the interior via the DC plug connectors
and the dust-protected threaded connections. The resulting condensate can cause damage to the device
during installation and start-up.
ü Keep the device closed during pre-assembly and do not open the connection area until you perform in-
stallation.
Seal off any plug-in connections and screw fittings using sealing covers.
Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently
before installation.
Immediately remove any moisture from the housing.
KACO blueplanet 50.0 TL3
Page 17