Connection Terminals; Notes; Technical Data - E. DOLD & SOHNE SAFEMASTER LG 5928 Manuel D'utilisation

Modules d'arrêt d'urgence avec temporisation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Connection Terminals

Terminal designation
A1(+)
A2 (-)
S11, S21, S13, S33
S12, S22, S32, S34
13, 14, 23, 24
37, 38

Notes

To select automatic restart terminals S13 - S34 must be bridged, S33 -
S34 must be opened. Open terminals S13 - S34 select manual restart, the
On-button must then be connected to S33 - S34.
Line fault detection on On-button:
The line fault detection is only active when the time delayed relais K1
K2
have released and then S12 (channel A) and S32 (channel B) are swit-
t
ched simultaneously. If the On-button is closed before S12, S32 is connec-
ted to voltage (also when line fault across On-button), the output contacts
will not close. The unit will not restart before the time delay is finished.
A line fault across the On-button which occurred after activation of the
relay, will be detected with the next activation and the output contacts will
not close. If a line fault occurs after the voltage has been connected to
S12, S32, the unit will be activated because this line fault is similar to the
normal On-function.
The unit can be operated with single channel and 2-channel operation
with cross fault monitoring. For connection please refer to application ex-
amples.
The terminal S21 permits the operation of the device in IT-systems with
insulation monitoring, serves as a reference point for testing the control
voltage and is used to connect the E-stop loop when cross fault monitoring
is selected.
Connecting the terminal S21 to the protective ground bridges the internal
short-circuit protection of Line A2(-). The short-circuit protection of line
A1(+) remains active.

Technical Data

Input
Nominal voltage U
:
N
Voltage range:
Nominal consumption:
Min. Off-time:
Control voltage S11:
Control current via S12, S32:
Min. voltage
to terminals S12, S32:
Short-circuit protection:
Overvoltage protection:
Output
Contacs:
Operating time typ. at U
:
N
manual start:
automatic start at U
:
N
Release delay typ. at U
:
N
in case of break of
supply voltage:
in case of break of
S12, S22 and S32:
Signal designation
+ / L
- / N
Inputs
Outputs
Positive driven NO contacts for
release circuit
Positive guided No contacts for
release delay circuit
DC 24 V
0.9 ... 1.1 U
N
approx. 3.5 W
1 s
DC 23 V at U
device not activated
N
each 40 mA at U
N
DC 19 V device not activated
Internal PTC
Internal VDR
2 NO contacts instantaneous, and
1 contact release delay
25 ms
100 ms
20 ms
10 ms
Technical Data
Time delay tv
(release delayed):
Repeat accuracy:
Contact type:
Nominal output voltage:
Max switching current:
Thermal current I
:
th
in 1 contact path:
13 / 14 or 23 / 24:
37 / 38:
Switching capacity
to AC 15
and
NO contact:
t
to DC 13
NO contacts:
Electrical life
to AC 15 at 2 A, AC 230 V:
Permissible operating
frequency:
Short circuit strength
max. fuse rating
13 / 14 or 23 / 24:
37 / 38:
Line circuit breaker:
Mechanical life:
General Data
Operating mode:
Temperature range
Operation:
Storage:
Altitude:
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x height x depth:
LG 5928:
LG 5928PC:
LG 5928PS:
16
Auxilary supply must be connected for
time delay
Time ranges:
0.1 ...
1 s
3.0 ...
30 s
0.3 ...
3 s
6.0 ...
60 s
0.5 ...
5 s
30 ... 300 s
1.0 ... 10 s
Other ranges or values on request
± 1 % of setting value
forcibly guided
AC 250 V
DC: see limit curve for arc-free operation
DC: see limit curve for arc-free operation
max. 8 A (see quadratic total current limit curve)
max. 6 A (see quadratic total current limit curve)
3 A / AC 230V
IEC/EN 60 947-5-1
2 A / DC 24 V
10
5
switching cycles IEC/EN 60 947-5-1
max. 360 switching cycles / h
with short release delay time
10 A gL
IEC/EN 60 947-5-1
4 A gL
IEC/EN 60 947-5-1
B 6 A
(max. short circuit current + 300 A)
10 x 10
6
switching cycles
Continuous operation
- 25 ... + 55 °C
- 25 ... + 85 °C
< 2.000 m
4 kV / 2
IEC 60 664-1
IEC/EN 61 326-3-1, IEC/EN 62 061
Limit value class B
EN 55 011
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplastic with V0 behaviour
according to UL subject 94
Amplitude 0.35 mm,
frequency 10 ... 55 Hz IEC/EN 60 068-2-6
25 / 055 / 04
IEC/EN 60 068-1
EN 50 005
Plus-minus terminal screws M3.5 box
terminals with wire protection
DIN rail
IEC/EN 60 715
approx. 210 g
22.5 x 90 x 121 mm
22.5 x 111 x 121 mm
22.5 x 104 x 121 mm
LG 5928 / 06.06.16 en / 704