Ul-Data; Standard Type; Ordering Example - E. DOLD & SOHNE SAFEMASTER LG 5928 Manuel D'utilisation

Modules d'arrêt d'urgence avec temporisation
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UL-Data

The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
:
Nominal voltage U
N
Ambient temperature:
Switching capacity:
Ambient temperature 45°C
Ambient temperature 55°C:
Wire connection:
Screw terminals fixed:
Plug in screw:
Plug in cage clamp:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

Standard Type

LG 5928.41/61 DC 24 V 1 ... 10 s
Article number:
• Output:
• 1 NO contacts release delayed
• Nominal voltage U
:
N
• Time delay tv:
• Width:
DC 24 V
-15 ... +55°C
Contact 13/14 and 23/24:
Pilot duty R300
6A 250Vac Resistive
6A 24Vdc Resistive or G.P.
Contact 37/38:
8A 250Vac Resistive
8A 24Vdc Resistive or G.P.
Contact 13/14 and 23/24:
Pilot duty R300
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
Contact 37/38:
7A 250Vac Resistive
7A 24Vdc Resistive or G.P.
60°C / 75°C copper conductors only
AWG 20 - 12 Sol/Str Torque 0.8 Nm
AWG 20 - 14 Sol Torque 0.8 Nm
AWG 20 - 16 Str Torque 0.8 Nm
AWG 20 - 12 Sol/Str
0061683
2 NO contacts instantaneous and
DC 24 V
1 ... 10 s
22.5 mm
Variants
LG 5928.41/61:
LG 5928.41/001/61:
LG 5928.41/100/61:
LG 5928.41/101/61:
Ordering example for variants:
LG 5928 .41
_ _ / _ _ _ /61 DC 24 V
17
with redundant time circuits to dis-
connect K1t and K2t, adjustable time.
Each time circuit operats one output relay
as LG 5928.41/61, but with fixed time
delay
Fixed times: 1 s, 3 s, 5 s, 10 s, 300 s
other values on request
as LG 5928.41/61, but deactivation of the
first time relay deactivates the second
time relay i. e. both relays switch off
simultaneously
as LG 5928.41/100/61, but with fix
time delay
Fixed times: 1 s, 3 s, 5 s, 10 s, 300 s
other times on request
1 ... 10 s
Fixed times
0.1 ...
1 s
0,3 ...
3 s
0.5 ...
5 s
1
...
10 s
30
... 300 s
Nominal voltage U
N
UL-approval
Variant, if required
Type of terminals
Without indication:
terminal blocks fixed
with screw terminals
PC (plug in cage clamp):
pluggable terminal blocks
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks
with screw terminals
Contacts
Type
LG 5928 / 06.06.16 en / 704