Function
Control and safety unit SH 1xx
Blink-code
x y y y y
No flame signal at the end of the safety time delay.
x x y y y
Stray light during the preventilation and the firing.
x x y y y – y y y y y
Manual safety shutdown (refer also to locking procedure).
Code
x
Short luminous signal
y
Long luminous signal
Break
Input signals required
Output signals
Limiter
1
Unit (and heater) energising
2
Motor and transformer energising
3
Fuel valve energising
4
Flame checking
Push on R
during ...
... less than 9
seconds...
... between 9
and 13
seconds...
... more than
13 seconds...
Description of the defect
Key word
Heater
Burner motor
Fuel valve
5
Firing transformer
shutdown - operating conditions
0
Control end - burner off
10
Defect mode
0301 / 13 010 881C
The SH 1xx oil-firing unit controls and monitors the
... causes ...
forced-air burner. The microprocessor-controlled
program sequence ensures the maximum consistency
of the time periods involved, regardless of fluctuations
in the power-supply voltage or ambient temperature.
release or locking
The design of the automatic firing unit protects it from
of the control unit.
the effects of brownouts, and also ensures that it is not
damaged by longer blackouts Whenever the supply
voltage drops below its rated minimum level, the
automatic system shuts down - even if no malfunction
signal has been emitted. The automatic system
erasing of the
switches itself back on again once the voltage has
statistics in the
returned to normal levels.
control unit.
Information system
The built-in visual information system keeps you
up-to-date regarding the causes of any safety
shutdown. The most recent cause of a malfunction is
no effect on the
logged, and the information can be reconstructed on
control unit.
startup of the system - even if there has been a power
failure in the meantime. In the event of a malfunction
occurring, the LED indicator in the "Reset" button R
lights up and stays permanently lit until the fault has
been acknowledged (i.e. until the error has been
cleared or the automatic system fault has been dealt
with. The light pauses every ten seconds to emit a
blink-code designed to indicate the cause of the
malfunction.
It is possible, using the readout device (available as an
optional accessory), to obtain further in-depth
information on the system's operating and malfunction
procedures.
Blocking and unblocking the system
The automatic unit can be blocked (corresponding to a
malfunction) and unblocked (cleared) by pressing the
"Reset" button R, provided the system is connected to
the power supply.
If the button is pressed during normal or startup mode,
the device goes into malfunction mode. If the button is
pressed with the system in malfunction mode, the
automatic unit is unblocked.
m
Always disconnect the power supply before
installing or removing the automatic unit. DO
NOT attempt to open the automatic unit, as
there are no user-serviceable parts inside.
Transformer
Flame control
tw
Holding time if heater present
tvl
Preventilation and pre-firing time
ts
Safety time
tn
Post-firing time
EN
Defect
Unlocking
37