Elco Klockner EK01B.4 L Notice D'emploi page 36

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Function
Pre-heating function
Operating function
Safety function
Pre-heating function
(only for EK01B.4L-H)
Whenever the system requires heat,
the first item to be activated is the
nozzle line heating system.
Once the oil pre-heating temperature is
reached, a thermostat in the nozzle line
heating system activates the program
sequence. Heating from a cold start
takes approximately two minutes.
36
Operating function
The control unit starts the program
sequence.
Motor starts, ignition system activates.
Pre-ventilation.
Solenoid valve 4 opens.
Flame begins to burn.
Ignition system disconnected.
0301 / 13 010 881C
Safety function
A safety shutoff is carried out:
If a flame indication is present during
pre-ventilation (detection of
unauthorised flame)
If no flame is present at the end of
the 5second safety period after
starting (fuel release)
If no flame is present after flame
failure during operation, and an
unsuccessful attempt has been made
to repeat the program.
The fault indicator lamp lights up
whenever a safety shutoff has been
carried out. The system can be reset
(once the fault has been remedied) by
pressing the reset button.
Schematic diagram
1
Oil burner pump
2
Oil pressure regulator
3
Oil pump
4
Solenoid valve
5
Nozzle line (with pre-heater
for EK01B.4L-H)
6
Burner head
7
Turbulator
8
Linearised air metering drum
9
Air shutter spring-loaded
(only EK01B.4/6)
10
Fan
11
Burner motor