Efrigerant Ines - Daikin DX17VSS Serie Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

• d
o not touch the SWItch WIth Wet fIngerS
WIth Wet fIngerS may reSult In electrIc Shock
• d
o not alloW chIldren to play on or around the unIt or It may
.
reSult In Injury
• t
he heat exchanger fInS are Sharp enough to cut
reSult In Injury If Improperly uSed
or cover the fInS When WorkIng around them
• d
o not touch the refrIgerant pIpeS durIng and ImmedIately
after operatIon aS the refrIgerant pIpeS may Be hot or cold
dependIng on the condItIon of the refrIgerant floWIng through
,
the refrIgerant pIpIng
compreSSor
. I
cycle partS
t may reSult In your handS gettIng BurnS or
froStBIte If you touch the refrIgerant pIpeS
gIve the pIpeS tIme to return to normal temperature or
,
muSt touch them
Be Sure to Wear proper gloveS
• I
nSulate SuctIon pIpIng to prevent condenSatIon
• B
e careful When tranSportIng the product
• t
ake adequate meaSureS to prevent the outdoor unIt from
BeIng uSed aS a Shelter By Small anImalS
Ing contact WIth electrIcal partS may reSult In malfunctIonS
,
. I
Smoke
or fIre
nStruct the cuStomer to keep the area around
.
the unIt clean
notice
• I
f the conventIonal refrIgerant and refrIgerator oIl are mIxed
r410a,
In
deterIoratIon WIll reSult
• t
hIS aIr condItIoner IS an applIance that Should not Be acceS
SIBle to the general puBlIc
• a
450
S deSIgn preSSure IS
-
of fIeld
InStalled pIpeS Should Be Selected In accordance WIth
,
the relevant local
State
r
l
efrIgerant
IneS
t
pve
he compreSSor
oIl for
ceptIBle to moISture aBSorptIon and could cauSe compreSSor
. d
faIlure
o not leave SyStem open to atmoSphere any longer
than neceSSary for InStallatIon
Use only refrigerant grade (dehydrated and sealed) copper
tubing to connect the air conditioner with the indoor evapora-
tor. After cutting the tubing, install plugs to keep refrigerant
tubing clean and dry prior to and during installation. Tubing
should always be cut square keeping ends round and free
from burrs. Clean the tubing to prevent contamination. The
liquid line must be insulated if more than 50 ft. of liquid line will
pass through an area that may reach temperatures of 30°F
or higher than outdoor ambient. Never attach a liquid line to
any uninsulated portion of the suction line.
Do NOT let refrigerant lines come in direct contact with plumb-
ing, ductwork, floor joists, wall studs, floors, and walls. When
running refrigerant lines through a foundation or wall, open-
ings should allow for sound and vibration absorbing material
to be placed or installed between tubing and foundation. Any
gap between foundation or wall and refrigerant lines should
be filled with a pliable silicon-based caulk, RTV or a vibration
cAUtion
. t
ouchIng a SWItch
.
,
and may
. t
o avoId Injury Wear glove
.
,
and other refrIgerant
. t
o avoId Injury
.
.
.
. S
mall anImalS mak
.
.
(3.1 mpa),
pSI
the Wall thIckneSS
,
.
and natIonal regulatIonS
cAUtion
r-410a
unItS IS extremely SuS
.
damping material. Avoid suspending refrigerant tubing from
joists and studs with rigid wire or straps that would come in
contact with the tubing. Use an insulated or suspension type
hanger. Keep both lines separate and always insulate the
suction line.
Insulation is necessary to prevent condensation from forming
and dropping from the suction line. Insulation tube with 3/8"
min. wall thickness is recommended. In severe conditions
(likely to exceed 86°F and a relative humidity of 80%) 1/2"
insulation may be required. Insulation must be installed in a
,
manner which protects tubing and connections from damage
and contamination.
Please use a HVAC flushing solvent to clean lineset of any
,
oil or debris from the existing system.
,
If you
note: If changing refrigerant, the indoor coil and metering
device must be replaced.
cond Unit
-
tons
,
3.5
4
5
x: Allowable combination
-
-
6
Allowable line set diameter
liquid
Suction
3/8
7/8
x
x
x
x
x
x
1 1/8
x
x
x