Daikin DX17VSS Serie Instructions D'installation page 47

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7-S
d
egment
ISplay
Screen 0 (display fAUlt code)
Setting
no.
1
Screen 1 (display fAUlt codeS)
Setting
no.
1
2
3
4
5
6
Screen 2 (Monitor Mode)
Setting
no.
1
Compressor operation time
2
Operation code
3
Compressor Reduction Mode
4
% Demand
5
Act % demand
6
Requested ID CFM
7
Reported ID CFM
8
Outdoor FAN RPM
9
Ta (Outdoor Air Temperature)
10
Td (Discharge Temperature)
11
Tm (Outdoor Coil Temperature)
13
Tl (Liquid Temperature)
14
Pressure Sensor
15
Ts (Suction Temperature)
contents
Fault code (present)
contents
Fault code (latest)
Fault code (2nd)
Fault code (3rd)
Fault code (4th)
Fault code (5th)
Fault code (6th)
contents
notes
notes
Latest
notes
unit: hr (Multiply by 200)
0: Stop
1: Cooling Start-up
3: Oil Return Operation
6: Cooling Operation
0:OFF, 1: ON
unit: %
(Cut off the decimal first place)
unit: %
(Cut off the decimal first place)
unit: CFM (Multiply by 10)
unit: CFM (Multiply by 10)
unit: RPM (Multiply by 10)
unit: F
unit: F
unit: F
unit: F
unit: PSI
unit: F