7) Maintenance and Disposal
!
This charter provides information about how to draw up a maintenance schedule, and the disposal of A60.
7.1) Maintenance
The automation must undergo maintenance work on a regular basis,
in order to guarantee prolonged lifetime.
The maintenance operations must be performed in strict
compliance with the safety directions provided in this
manual and according to the applicable legislation and
standards.
If other devices are present, follow the directions provided in the cor-
responding maintenance schedule differents from A60.
7.2) Disposal
As in the case of installation, at the end of the product lifetime, dis-
posal procedures must be carried out by qualified personnel.
This product comprises various types of materials, some of which
can be recycled while others must be disposed of. Check informa-
tion on the recycling and disposal procedures according to local leg-
islation for this product category.
!
Some parts of the product may contain pollutant or
hazardous substances; if disposed of into the environment
these may constitute a serious risk of damage to the envi-
ronment and public health.
8) Accessories
RADIO card
The control unit features a connector for plugging in an SM radio
card , which activates the inputs and allows the control unit to be
remote-controlled through a transmitter.

9) Technical characteristics

With the aim of improving products, Nice S.p.a reserves the right to modify technical characteristics at any time without notice, while main-
taining the same functionalities and intended use.
All technical characteristics stated refer to an ambient temperature of 20°C (±5°C).
Model type:
Power
Maximum actuators power
Maximum flashing light power
Maximum frequency of operating cycles
Maximum time of continuous operation
Maximun current accessories (24 Vac)
Maximun current phototest output
Gate open indicator max. power SCA (24Vac)
Maximun electric lock power 12 Vac
Working time
Pause time
TRA opening delay time
TRC closing delay time
BALANCING manoeuvre times
Force adjustment
Operating temperature
Size
Weight
Protection level
14
1. Is requires scheduled maintenance work every 6 months or
10.000 manoeuvres (max.) after previous maintenance.
2. Disconnect all power supplies.
3. Check for any deterioration of the components which form the
automation, paying particular attention to erosion or oxidation of
the structural parts. Replace any parts which are below the
required standard.
4. Connect the electric power sources up again, and carry out the
testing and checks stated in Paragraph "6 Testing".
As indicated by the symbol in figure nev-
er dispose of this product in domestic
waste. Apply "classified waste collection"
procedures for disposal in accordance
with local regulations or return the prod-
uct to the retailer when purchasing a new
model.
Local regulations may envisage serious fines in the event of illegal
disposal of this product.
output 1 STEP-BY-STEP
output 2 Open for pedestrians
output 3 Open
output 4 Close
A60
230 Vac ± 10%, 50 - 60 Hz
300 W [1,3 A]
unlimited
unlimited
from 2,5 to 40 sec. (from 40 to 80 sec. with TLM)
from 5 to 80 sec.
0 or from 2.5 to 12 sec.
0 or from 2.5 to 12 sec.
from 0 to 8 sec.
from 0 to 100 %
-20 ÷ 50 °C
280 x 220 x 110 mm
IP 55 (container undamaged)
A60/V1
120 Vac ± 10%, 50 - 60 Hz
300 W [2,5 A]
100W
200 mA
75 mA
2 W
15 VA
1,9 Kg