ABB REF 610 Manuel De Référence page 103

Masquer les pouces Voir aussi pour REF 610:
Table des Matières

Publicité

1MRS755566
Relais de protection de ligne
Manuel de référence technique
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY
Reports Digital Input Change Events when
no specific variation requested
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the
other (depends on default variation)
Sends Unsolicited Responses
Never
Configurable
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Default Counter Object/Variation
No Counters Reported
Configurable, default object and variation
Default Object 20
Default Variation 2
Point-by-point list attached
Sends Multi-Fragment Responses
Table 4.1.16.4-1 Supported function codes
Code Function
Transfer Function Codes
0
Confirm
1
Read
2
Write
Control Function Codes
3
Select
Reports time-tagged Digital Input Change
Events when no specific variation requested
Never
Binary Input Change With
Time
Binary Input Change With
Relative Time
Configurable, depends on
objects basic variation
(variation used at
initialization)
Sends Static Data in Unsolicited Responses
Never
When Device Restarts
When Status Flags Change
No other options are permitted.
Counters Roll Over at
No Counters Reported
Configurable (attach explanation)
16 Bits (Counters 6...9)
32 Bits, but roll-over bits not used
Other value: 999 (Counters 0...5) and
255 (Counters 10...21)
Point-by-point list attached
Yes
No
Description
Message fragment confirmation
No response
Request objects from outstation
Respond with requested objects
Store specified objects to outstation
Respond with status of operation
Select output point of outstation
Respond with status of control point
REF 610
Supported
Yes
Yes
Yes
No
103