Chauvin Arnoux C.A 6545 Notice De Fonctionnement page 68

Masquer les pouces Voir aussi pour C.A 6545:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
 Insulation Measurements
CHAUVIN ARNOUX C.A 6547
Instrument number: 000 001
INSULATION RESISTANCE TEST
PURPOSE: 01
TEST: 01
Description: .................................................
......................................................................
Date: ..........................................31.03.1998
Starting time: .....................................14h55
Running time: ............. 15 min. 30 seconds.
Temperature: ............................. °C .........°F
Relative humidity: .................................... %
Test voltage: .................................... 1000 V
Insulation resistance (R): ........... 385 GOhm
DAR: ...................................................1.234
PI: .......................................................2.345
DD: ..............................................................
Capacitance: ...........................................µF
I residual: ................................................ nA
Comments: ..................................................
......................................................................
Date of next test: .......................... /..../.......
After a "Programmed time test" other results are printed (intermediate samples):
Time
Resistance
00: 30
35.94 GOhm
01: 00
42.00 GOhm
01: 30
43.50 GOhm
etc.
A line for the signature of the operator appears at the end of printing.
6.3.2. PRINTING OF STORED DATA (PRINT MEM KEY)
This is used to print the content of the unit's RAM.
The small display indicates 01: 01 for the OBJ: TEST number (print starting address).
The main display indicates the last record in the memory (end print address).
For example 12:06.
"12" above OBJ symbol fl ashes and the normal modifi cation procedure must be used (
to defi ne the start/end of printing addresses.
To exit without printing, change the position of the rotary switch.
To start printing, press again on the PRINT key.
To stop printing, change the position of the rotary switch.
The printing of each data group is limited to the main results.
(printed only in MR mode)
Voltage
1005 V
1005 V
1005 V
68
and
keys)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

C.a 6547

Table des Matières