4.3 Connecting AC cables
The Quattro is a safety class I product (supplied w ith an ground terminal for safety
purposes). Its AC input and/or output terminals and/or grounding point on
the outside of the product must be provided with an uninterruptable
grounding point for safety purposes. See the following instructions in this
regard.
The Quattro is provided w ith a ground relay (see appendix) that autom atically
connects the N output to the casing if no external AC supply is available. If
an external AC supply is provided, the ground relay w ill open before the input
safety relay closes (relay H in appendix B). This ensures the correct operation of
an earth leakage circuit breaker that is connected to the output.
In a fixed installation, an uninterruptable grounding can be secured by means of
the grounding w ire of the AC input. Otherw ise the casing must be grounded.
In a mobile installation (for example, w ith a shore current plug), interrupting the
shore connection w ill simultaneously disconnect the grounding connection. In that
case, the casing must be connected to the chassis (of the vehicle) or to the hull or
grounding plate (of the boat).
In general, the connection described above to shore connection grounding is not
recommended for boats because of galvanic corrosion. The solution to this is
using an isolating transformer.
AC-in-1 (see appendix A)
If AC voltage is present on these terminals, the Quattro w ill use this connection. Generally a generator w ill be connected to AC-
in-1.
The AC-in-1 input must be protected by a fuse or m agnetic circuit breaker rated at 50A or less, and cable cross-
section m ust be sized accordingly. If the input AC supply is rated at a low er value, the fuse or magnetic circuit breaker
should be dow n sized accordingly.
AC-in-2 (see appendix A)
If AC voltage is present on these terminals, the Quattro w ill use this connection, unless voltage is also present on
AC-in-1. The Quattro w ill then automatically select AC-in-1. Generally the mains supply or shore voltage w ill be connected
to AC-in-2.
The AC-in-2 input must be protected by a fuse or m agnetic circuit breaker rated at 30A or less, and cable cross-
section m ust be sized accordingly. If the input AC supply is rated at a low er value, the fuse or magnetic circuit breaker
should be dow n sized accordingly.
Note: The Quattro may not start when AC is present only on AC-in-2, and DC battery voltage is 10% or m ore below
nom inal (less than 11 Volt in case of a 12 Volt battery).
Solution: connect AC power to AC-in-1, or recharge the battery.
AC-out-1 (see appendix A)
The AC output cable can be connected directly to the terminal block "AC-out".
With its Pow erAssist feature the Quattro can add up to 3kVA (that is 3000 / 230 = 13A) to the output during periods of peak
pow er requirement. Together w ith a maximum input current of 50A this means that the output can supply up to 50 + 13 = 63A.
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in
series with the output, and cable cross-section must be sized accordingly. The maximum rating of the fuse or circuit
breaker is 63A.
AC-out-2 (see appendix A)
A second output is available that disconnects its load in the event of battery operation. On these terminals, equipment is
connected that m ay only operate if AC voltage is available on AC-in-1 or AC-in-2, e.g. an electric boiler or an air
conditioner. The load on AC-out-2 is disconnected immediately w hen the Quattro switches to battery operation. After AC power
becomes available on AC-in-1 or AC-in-2, the load on AC-out-2 w ill be reconnected with a delay of approximately 2 minutes.
This to allow a genset to stabilise.
AC-out-2 can support loads of up to 25A. An earth leakage circuit breaker and fuse rated at max. 25A must be connected in
series w ith AC-out-2.
Procedure
Use three-core cable. The connection terminals are clearly encoded:
PE: earth
N: neutral conductor
L: phase/live conductor